Appendix D—Modbus Register Map
314 Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
346 Run Time Lifetime UINT32 RO
Units: seconds
Backup Mem
Total motor run time in seconds
348 Number Starts Lifetime UINT32 RO
Manufacturing Lock
Backup Mem
Total Number of Motor Starts in lifetime, not resettable.
350 Operating Seconds Lifetime UINT32 RO
Units: seconds
Backup Mem
Total number of Seconds the motor has been running. Not resettable.
352 Run Time Resettable UINT32 RW NV
Default: 0
Units: seconds
Admin Lock
USB Lock
Backup Mem
Total motor run time in seconds (Resettable). Resettable values can be
zero-ed out by the user at any time.
354 Number Starts Resettable UINT32 RW NV
Default: 0
Admin Lock
USB Lock
Backup Mem
Total number of motor starts (Resettable).
356 Operating Seconds
Resettable
UINT32 RW NV
Default: 0
Units: seconds
Backup Mem
Total number of Seconds the motor has been running since this value
was last reset. This value is resettable.
358 Contactor Operations Last
Hour
UINT16 RO
Backup Mem
Number of Contactor Operations During the Last Hour
359 Last Run Time UINT32 RO
Default: 0
Units: seconds
Duration in Seconds of the Last Start-to-Stop Motor Run Time
361 Last Starting Time UINT16 RO
Default: 0
Units: seconds
The amount of time the motor took to get up to speed on the last start.
362 I Average % of FLA UINT16 RO
Units: %
Monitored Average Motor Current as Percentage of FLA (Nominal
Current)
363 Current Demand Value UINT32 RO
Units: W
Latest estimate of the Demand measured over the demand window
duration.
365 Demand (Resettable) UINT32 RW NV
Default: 0
Range: 0 to 0
Units: W
Admin Lock
USB Lock
Backup Mem
Peak Demand, User Resettable. The peak demand is updated if the
new demand calculated over the demand window is greater than the
previous peak.
367 Peak Demand Time Stamp UINT32 RO
Default: 0
Units: seconds
Admin Lock
USB Lock
Backup Mem
Peak Demand Time Stamped (in Unix time)
Table 128. C445 Modbus Register Map, continued
Register Name Attribute Description