Appendix D—Modbus Register Map
322 Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com
714 Local/Remote PowerUp
Behavior
UINT8 RW NV
Default: 2
Enum
Config CRC
Admin Lock
USB Lock
Backup Mem
Select the Local/Remote mode the Base Control Module will power up in.
Selections: 0: Local control is active control on power up, 1: Remote
control is active control on power up, 2: Hold last control state on
power up.
715 Q1 Function Select UINT16 RW NV
Default: 54
Enum
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
Output Function Select for General Purpose Output 1. Available when this
output is not used by the Operation Mode. Default = none, If used by the
Application Mode = Reserved. A soft reset is required after modifying this
parameter.
Table 128. C445 Modbus Register Map, continued
Register Name Attribute Description
Value Description
0 Local control is active control on power-up
1 Remote control is active control on power-up
2 Hold last control state on power-up
Value Description
0None
1 Fault Reason Type - Load fault (Power based)
2 Fault Reason Type - Supply fault (Voltage based)
3 Fault Reason Type - Motor fault (Current based)
4 Tripped Status Bits - PTC
5 Tripped Status Bits - Phase rotation mismatch
6 Tripped Status Bits - Stall
7 Tripped Status Bits - Overload
8 Tripped Status Bits - Starts limit exceeded
9 Tripped Status Bits - Low power
10 Tripped Status Bits - High power
11 Tripped Status Bits - Under current
12 Tripped Status Bits - Frequency deviation slow
13 Tripped Status Bits - Frequency deviation fast
14 Tripped Status Bits - Voltage unbalan
ce
15 Tripped Status Bits - Voltage phase loss
16 Tripped Status Bits - Power factor deviation
17 Tripped Status Bits - Jam
18 Tripped Status Bits - Instantaneous over current
19 Tripped Status Bits - Current unbalance
20 Tripped Status Bits - Current phase loss
21 Tripped Status Bits - Ground fault
22 Motor Control Status - Motor at speed
23 Motor Control Status - Ready
24 Motor Control Status - Inhibited
25 Motor Control Status - Warning
26 Motor Control Status - Faulted
27 Motor Control Status - Remote enabled
28 Motor Control Status - Running 2
29 Motor Control Status - Running 1