Appendix D—Modbus Register Map
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 339
746 Control User Interface User
LED 3 Purpose
UINT16 RW NV
Default: 1 Enum
Config CRC
Admin Lock
USB Lock
Backup Mem
User Defined LED 3 Function Selection - Default: Power Related Fault.
Applies only to C445UC… Control Family of User Interfaces, continued.
Table 128. C445 Modbus Register Map, continued
Register Name Attribute Description
Value Description
24 Motor Control Status - Inhibited
25 Motor Control Status - Warning
26 Motor Control Status - Faulted
27 Motor Control Status - Remote enabled
28 Motor Control Status - Running 2
29 Motor Control Status - Running 1
30 Warning Status Bits - PTC
31 Warning Status Bits - Phase rotation mismatch
32 Warning Status Bits - Stall
33 Warning Status Bits - Overload
34 Warning Status Bits - Starts limit exceeded
35 Warning S
tatus Bits - Low power
36 Warning Status Bits - High power
37 Warning Status Bits - Under current
38 Warning Status Bits - Frequency deviation slow
39 Warning Status Bits - Frequency deviation fast
40 Warning Status Bits - Voltage unbalance
41 Warning Status Bits - Voltage phase loss
42 Warning Status Bits - Power factor deviation
43 Warning Status Bits - Jam
44 Warning Status Bits - Instantaneous over current
45 Warning Status Bits - Current unbalance
46 Warning Status Bits - Current phase loss
47 Warning Status Bits -
Ground current
48 Warning Status Bits - Reserved
49 Warning Status Bits - Over voltage
50 Warning Status Bits - Under voltage
51 Tripped Status Bits - Under voltage
52 Tripped Status Bits - Over voltage
53 Tripped Status Bits - Reserved
54 Base Control Module Field Output control word - Bit 0
55 Base Control Module Field Output control word - Bit 1
56 Base Control Module Field Output control word - Bit 2
57 Base Control Module Field Output control word - Bit 3
58 Shunt trip output bit - Shunt trip output bit
59 Warning Reason - HRGF pulse detection
60 Warning Reason - Peak demand
61 Digital Input Status - Base Control Module Input I4
62 Digital Input Status - Base Control Module Input I3
63 Digital Input Status - Base Control Module Input I2
64 Digital Input Status - Base Control Module Input I1
65 Fail Safe - Ground current fault
65535 Reserved