Appendix D—Modbus Register Map
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 345
771 Stop LED Color UINT8 RW NV
Default: 0
Enum
Config CRC
Admin Lock
USB Lock
Backup Mem
MUI Stop Button LED Color
772 Auto LED Color UINT8 RW NV
Default: 2
Enum
Config CRC
Admin Lock
USB Lock
Backup Mem
MUI Auto Button LED Color
773 Start Button Debounce UINT16 RW NV
Default: 50
Units: mSec
Config CRC
Admin Lock
USB Lock
Backup Mem
MUI start button debounce time in milliseconds.
774 Stop Button Debounce UINT16 RW NV
Default: 50
Units: mSec
Config CRC
Admin Lock
USB Lock
Backup Mem
MUI stop button debounce time in milliseconds.
775 Auto Button Debounce UINT16 RW NV
Default: 50
Units: mSec
Config CRC
Admin Lock
USB Lock
Backup Mem
MUI auto button debounce time in milliseconds.
776 Reset Button Debounce UINT16 RW NV
Default: 250
Units: mSec
Config CRC
Admin Lock
USB Lock
Backup Mem
MUI reset button debounce time in milliseconds.
777 Enable Fieldwire Inputs BYTE RW NV
Default: 0x0F
Bitfield
Config CRC
Admin Lock
USB Lock
Backup Mem
BCM Fieldwire Control Inputs Enable
Table 128. C445 Modbus Register Map, continued
Register Name Attribute Description
Value Description
0 Green
1Red
2Amber
3White
255 Off
Value Description
2Amber
3White
255 Off
Bit Description Coil
0 Input1 (I1) 12417
1 Input1 (I2) 12418
2 Input1 (I3) 12419
3 Input1 (I4) 12420