Appendix D—Modbus Register Map
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 349
778 Run Interlock inputs BYTE RW NV
Array size: 18
Default:
0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0
Bitfield
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
Define which inputs are run interlock inputs, If set, corresponding input
must be enabled to run motor, continued.
Define Run Interlock Inputs.
787 Remote Switch from
Fieldbus
BOOL RW NV
Default: 0
Range: 0 to 1
Config CRC
Admin Lock
USB Lock
Backup Mem
Remote Switch from Fieldbus - when set to true, allows fieldbus to set
control mode to remote Remote Switch from Fieldbus.
900 FLA Motor1 Scaled UINT16 RW NV
Default: 101
Range: 1 to 65535 (RW)
Units: sc
aled A
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
Motor1 Overload FLA (Nominal Current) Scaled - Scaled Full Load
Amperes for the motor from the motor nameplate. If this is an application
with a 2 motor profile, this is the first motor. Scaled by parameter “I Scale
Factor”.
901 FLA Motor2 Scaled UINT16 RW NV
Default: 101
Range: 1 to 65535 (RW)
Units: scaled A
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
Motor2 Overload FLA (Nominal Current) Scaled - Scaled Full Load
Amperes for the motor from the motor nameplate. If this is an application
with a 2 motor profile, this is the second motor. Scaled by parameter “I
Scale Factor”.
902 Rated Service Factor
Scaled
UINT8 RW NV
Default: 115
Range: 100 to 255
Units: 0.01%
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
This is the percentage of overloading the motor can handle for short
periods of time when operating normally within the correct voltage
tolerances. This value is from the motor nameplate.
Table 128. C445 Modbus Register Map, continued
Register Name Attribute Description
Bit Description Coil
136 ELC input x170 12569
137 ELC input x171 12570
138 ELC input x172 12571
139 ELC input x173 12572
140 ELC input x174 12573
141 ELC input x175 12574
142 ELC input x176 12575
143 ELC input x177 12576