Appendix D—Modbus Register Map
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 351
913 Rated Power Factor Scaled SINT16 RW NV
Default: 8350
Range: 5000 to 10000
Units: 0.01%
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
Motor Rated Power Factor in Percent from the motor nameplate.
914 Rated Speed Motor1 UINT16 RW NV
Default: 1750 (RW)
Range: 300 to 3600 (RW)
Units: RPM
Config CRC
Admin Lock
USB Lock
Backup Mem
RPM nameplate rating for motor winding#1 (Used in all control profiles).
915 Rated Speed Motor2 UINT16 RW NV
Default: 1750 (RW)
Range: 300 to 3600 (RW)
Units: RPM
Config CRC
Admin Lock
USB Lock
Backup Mem
RPM nameplate rating for motor winding#2 (Used in star/delta, two speed
and dahlander profiles).
916 Rated Efficiency **removed
from PCTool**
UINT16 RW NV
Default: 8500
Range: 5000 to 10000
Units: 0.01%
Config CRC
Admin Lock
USB Lock
Backup Mem
Motor rated efficiency in scaled percent (0.01%).
917 Rated Stator Resistance
Scaled
UINT16 RW NV
Default: 280
Units: mOhms
Config CRC
Admin Lock
USB Lock
Backup Mem
Motor Rated Stator Resistance from motor nameplate in milliohms.
918 CT Ratio Primary UINT16 RW NV
Default: 1
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
CT Ratio - Primary (Only used with external Current Transformers)
919 CT Ratio Secondary UINT16 RW NV
Default: 1
Config CRC
Run Lock
Admin Lock
USB Lock
Backup Mem
CT Ratio - Secondary (Only used with external Current Transformers)
Table 128. C445 Modbus Register Map, continued
Register Name Attribute Description