Appendix D—Modbus Register Map
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 399
2559 Fault/Warning configuration BYTE RW NV
Array size: 4
Default: 0
Bitfield
Config CRC
Admin Lock
USB Lock
Backup Mem
Fault/Warning configuration - When a bit is set to 0, a fault is thrown,
when set to 1, a warning is thrown.
2561 Logic error info - Program Id UINT16 RO
Default: 0
Logic error info - Program Id
Logic error info - Program Id
2562 Logic error info - Program
Counter
UINT32 RO
Default: 0
Logic error info - Program Counter
Logic error info - Program Counter
2564 Logic error info - Error Data UINT32 RO
Default: 0
Logic error info - Error Data
Logic error info - Error Data
2566 Logic Run Control BYTE RW NV
Default: 0
Bitfield
Config CRC
Admin Lock
USB Lock
Backup Mem
Logic Run Control
2567 Logic Run Status BYTE RO
Default: 0
Bitfield
Logic Run Status
2568 ELC IO Speciality Module
config lo
cation
UINT8 RW NV
Default: 0
Enum
Admin Lock
Backup Mem
ELC IO Speciality Module config location
Table 128. C445 Modbus Register Map, continued
Register Name Attribute Description
Bit Description Coil
0 Logic program underrun 40929
1 Logic program overrun 40930
2 Logic task watchdog 40931
3 Logic instruction invalid instance number 40932
4 Logic instruction invalid argument 40933
5 Logic math - divide by zero 40934
6 Logic math - underflow 40935
7 Logic math - overflow 40936
8 ELC IO Comm loss 40937
9 ELC IO Comm error 40938
10 Generic Modbus slave comm loss 40939
11 Generic Modbus slave comm error 40940
12 Logic Progr
am accessing ELC IO but ELC IO not
configured
40941
Bit Description Coil
0 Run 41041
Bit Description Coil
0 Logic Running 41057
Bit Description Coil
0 C445 ELC10