Appendix D—Modbus Register Map
Power Xpert C445 Global Motor Management Relay MN042003EN—January 2019 www.eaton.com 409
4019 RTC DST Start UINT8 RW NV
Array size: 5
Default: 3, 2, 7, 2, 0
Config CRC
Admin Lock
USB Lock
Backup Mem
Real Time Clock Manual Daylight Savings Time Rule Start date/time
(Element 0 = month, Element 1 = week, Element 2 = weekday, Element 3 =
hour, Element 4 = minute).
Array of 3 registers
4022 RTC Month and Date UINT8 RO
Array size: 2
Real Time Clock Month and Date
Array of 1 registers
4023 RTC Time Zone Ahead of
UTC
UINT8 RW NV
Default: 0
Enum
Config CRC
Admin Lock
USB Lock
Backup Mem
Real Time Clock calculation for Time Zone ahead of UTC. If true,
UTC+hh:mm; otherwise UTC-hh:mm
4024 RTC Time Zone hh mm UINT8 RW NV
Array size: 2
Default: 0
Config CRC
Admin Lock
USB Lock
Backup Mem
Time zone assignment (UTC+/-hh:mm). Where 0xhhmm. Element [0] =
Minutes Element [1] = Hours
Array of 1 register
5000 Admin Password UINT32 RW
Default: 0x00000000
Config CRC
Admin Lock
USB Lock
Backup Mem
Set administrator password (0x00000000 means no password)
5002 Admin Login UINT32 RW Log in with administrator password
5004 USB Password UINT32 RW
Default: 0x00000000
Config CRC
Admin Lock
USB Lock
Backup Mem
Set USB port password (0x00000000 means no password)
5006 USB Login UINT32 RW Log in with USB Port administrator password
5008 Run Lock Override BOOL RW NV
Default: 0
Config CRC
Admin Lock
USB Lock
Backup Mem
When the motor is either running or is being commanded to run, certain
protection and control parameters are locked. To disable this lock and
allow parameters to be adjusted during motor run time, check this box. To
restrict access during run time, uncheck this box. It is not recommended
to change configuration parameters while running.
5009 Motor Running Parameter
Access Lock
INTERNAL
UINT8 RO
Indicates whether the Motor Running Parameter Access Lock is
currently locked. If this parameter is high then the lock is active and the
run lock parameters will be in a read only state.
5010 Param Lock INTERNAL
UINT8 RO
Indicates whether the Admin Password Parameter Access Lock is
currently locked. If this parameter is high then the lock is active and the
admin lock parameters will be in a read only state.
5011 USB Param Lock State INTERNAL
UINT8 RO
When this bit is high the USB Parameter Access lock is enabled.
Parameters covered by the USB Param lock will be read only during this
time.
Table 128. C445 Modbus Register Map, continued
Register Name Attribute Description
Value Description
0 UTC - hh: mm
1 UTC + hh: mm