Menu structure UA 300 D Controller type UA 111 XP
68
Version 2.03 27. Juni 2008
S Screen 1−7 Cooling Zone 2
COOLING 2 POS: XXXXX
Cooling XXX Current ON/OFF status of cooling Zone 2 Terminals 35/36/38
Run Time XX % Cooling relay on time during last day (00:00 − 24:00 hours)
Starts X Cooling relay actuations during last day
Setpoint R2.8 XXX °C Supply air temperature setpoint for comparison
Hystersis R2.8 XXX K Supply air temperature hysteresis setpoint
S Screen 1−8 Defrost Zone 2
DEFROST 2 POS: XXXXX
Defrost 2 XXX Current ON/OFF status of defrosting Zone 2
Def. End. Tmp. XXX °C Defrost termination temperature for comparison
Last DefrstWe XX hh:mm Day and time of last defrost cycle started
7.2.3 Menu 2 Setpoints
SETPOINTS POS: XXXXX
1 Cooling Continue to Screen 2−1; Special case: when single−zone operation is set (Screen 6−1) and
setpoint toggle is disabled (Screen 3−3) Continue to Screen 2−1−1
2 Defrost Continue to Screen 2−2; Special case: when single−zone operation is set (Screen 6−1) and
setpoint toggle is disabled (Screen 3−3) Continue to Screen 2−2−1
3 Not used with this controller type
4 Alarm Continue to Screen 2−4; Special case: when single−zone operation is set (Screen 6−1) and
setpoint toggle is disabled (Screen 3−3) Continue to Screen 2−4−1
5 Compressor Continue to Screen 2−5
S Screen 2−1 Cooling
COOLING POS: XXXXX
1 Zone 1 Continue to Screen 2−1−1
2 Zone 2 Continue to Screen 2−1−2; shown only when two−zone operation is set (Screen 6−1)
3 Zone 1A Altern. Continue to Screen 2−1−3; shown only when setpoint toggle is enabled (Screen 3−3)
4 Zone 2A Altern. Continue to Screen 2−1−4; shown only when two−zone operation is set (Screen 6−1) and only
when setpoint toggle is enabled (Screen 3−3)