Menu structure UA 300 D Controller type UR 141
88
Version 2.03 27. Juni 2008
ALARM 1A POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High Temperature
alarm is generated
−30..30 −12 °C
Low Temp Setp. XX K Low temperature setpoint (difference below temperature
control setpoint) at which Low Temperature alarm is gene-
rated
−−, 0..6 2 K
S Screen 2−4−4 Zone 2A Altern.
ALARM 2A POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High Temperature
alarm is generated
−30..30 10 °C
Low Temp Setp. XX K Low temperature setpoint (difference below temperature
control setpoint) at which Low Temperature alarm is gene-
rated
−−, 0..6 2 K
7.3.4 Menu 3 Clock
CLOCK POS: XXXXX
1 Current Time Continue to Screen 3−1
2 Defrost timer Continue to Screen 3−2
3 Toggle Setpoints Continue to Screen 3−3
S Screen 3−1 Current Time
Time default is set by the time master (CI 3000, AL 300) when CAN bus is connected. Any entry
made will then be overwritten by the default value.
CLOCK POS: XXXXX Entry Default
Date: XX dd.mm.yy Display and enter current weekday, date dd.mm.yy
Time: hh.mm Display and enter current time hh.mm
Daylight Saving X Display and enter automatic daylight saving change (Y/N) ↑, ↓, (Y/N) J