Menu structure UA 300 D Controller type UA 111 XP
73
E 2007 − ECKELMANN | BERLINER STRASSE 161 | 65205 WIESBADEN | FON +49(0)611 7103-0 | FAX 49(0)611 7103-133 | eckelmann.de
Version 2.03 27. Juni 2008
7.2.4 Menu 3 Clock
CLOCK POS: XXXXX
1 Current Time Continue to Screen 3−1
2 Defrost timer Continue to Screen 3−2
3 Toggle Setpoints Continue to Screen 3−3
S Screen 3−1 Current Time
Time default is set by the time master (CI 3000, AL 300) when CAN bus is connected. Any entry
made will then be overwritten by the default value.
CLOCK POS: XXXXX Entry Default
Date: XX dd.mm.yy Display and enter current weekday, date dd.mm.yy
Time: hh.mm Display and enter current time hh.mm
Daylight Saving X Display and enter automatic daylight saving change (Y/N) ↑, ↓, (Y/N) J
S Screen 3−2 Defrost timer
DEFROST TIMER POS: XXXXX Entry Default
Defrost timer XXX Defrost initiation via input D11/12 (EXT) or internal (INT) ↑, ↓,
(EXT, INT)
INT
Safe Defr Time XXX m Safe defrost time for maximum allowed duration of defro-
sting (used only for internal defrosting)
0..120 60 min
Defr. 1 xxxxx hh:mm Defrost start time with internal defrosting; weekday, time;
shown only when internal defrosting is activated (Screen
3−2)
↑, ↓,
(Mo−Su etc.)
or numbers
(hh:mm)
Mo−Su
06:00
Defr. 2 xxxxx hh:mm Defrost start time with internal defrosting; weekday, time;
shown only when internal defrosting is activated (Screen
3−2)
↑, ↓,
(Mo−Su etc.)
or numbers
(hh:mm)
Mo−Su
18:00
...
Defr. 14 xxxxx hh:mm
Manual Defrost XXX Status (OFF/ON) for supplementary manual defrosting *) ↑, ↓,
(ON/OFF)
OFF
*) Parameter automatically set to ON for safe defrost time at first start.