Version 2.02 15.05.2007 Installation and Startup of VS 3000
56
4. Pull connector (1) out to rear and pull out lower circuit board (2).
5. Pull battery (1) upwards out of holder and dispose of it in regulation manner:
Do not grip the new battery with metal pliers, as it might short-circuit and be destroyed.
- Wipe the new battery with a clean, dry cloth.
- Do not touch the edge contact faces.
7. Grip the new battery with a cloth and insert it in the battery holder.
8. Re-assemble in the reverse order. Reconnect all connectors.
9. Reconnect pack controller to power.
10. Provided configuration of the CI 3000 Store Computer is not changed, the pack controller will be
re-detected automatically via the CAN bus. Date, time and automatic daylight saving change will be
set automatically by central time synchronization.
Messages and/or alarms displayed when restarting the pack controller must be checked out on the CI
3000 Store Computer or AL 300 Operator Terminal!
First start should be performed on the pack c ontroller after replacing the battery. All variables, ex-
cept the parameters, are reset to zero. Data should be backed up with the LDSWin Software prior
to performing first start.