Additive type Supplier and specications Max. concentration Application
Corrosioninhibitors Sentinel X100 Corrosion resistant
protection agent of CH systems
Kiwacertied
1-2 l/100 litres CH water content Aqueous solution of organic
and inorganic agents preventing
corrosion and scale forming
Fernox F1 Protector Corrosion
resistant protection agent of CH
systems
KiwacertiedKIWA-ATAK62581,
BelgaquacertiedCatIII
500 ml can or 265 ml Express /
100 litres CH water content
Preventing corrosion and scale
forming
Anti-freeze Kalsbeek
Monopropyleneglycol /
propane-1,2-diol
+inhibitors
AKWA-Colpro KIWA-ATA Nr. 2104/1
50% w/w Anti-freeze
Tyfocor L
Monopropyleneglycol /
propane-1,2-diol
+inhibitors
50% w/w Anti-freeze
Sentinel X500
Monopropyleneglycol+inhibitors
Kiwacertied
20-50% w/w Anti-freeze
Fernox Alphi 11
Monopropyleneglycol+inhibitors
KiwacertiedKIWA-ATAK62581,
BelgaquacertiedCatIII
25-50% w/w Anti-freezeincombinationwithF1
Protector
System cleaners Sentinel X300
Solution of phosphate, organic
heterocyclic compounds, polymers
andorganicbases
Kiwacertied
1 litre / 100 litres For new CH installations
Removesoils/greaseandow
control agents
Sentinel X400
Solution of synthetic organic
polymers
1-2 litres / 100 litres For cleaning existing CH-installati-
ons Removes sediments.
SentinelX800Jeto
Aqueous emulsion of dispersants,
moisteningagentsandinhibitors
1-2 litres / 100 litres For cleaning new and existing
CH-installations Removes iron
and lime-related sediments.
Fernox F3 Cleaner
Liquid pH neutral universal cleaner
for pre-commissioning new systems
500 ml / 100 litres For cleaning new and existing
CH-installations Removes sludge,
limescaleandotherdebris.
Fernox F5 Cleaner, Express
pH neutral universal cleaner
concentrate for pre-commissioning
new systems
295 / 100 litres For cleaning new and existing
CH-installations Removes sludge,
limescaleandotherdebris.
Installation
System water additives
The system water additives, which are
listedinthetable,havebeenreleased
bythemanufacturerandtakeinto
consideration the indicated dosage
quantities.
In case of a wrong use, and if the
maximum concentration quantities are
exceeded, then the guarantee for all
components that come in contact with
heating water are null and void.