EasyManua.ls Logo

elco TRIGON L PLUS - Flue Gas and Air Ducts

elco TRIGON L PLUS
108 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
Flue gas connection
WerecommendtheuseofELCO’s
comprehensiverangeofuegas
components.
For further information, please see the
installation instructions:
- ELCO wall terminals
- ELCO roof terminals
- ELCOuepipecomponents,both
individualpipesandconcentrictubes.
Regulationsabouttheconstruction
andinstallationofuegassystems
aredi󰀨erentfromcountrytocountry.
Itmustbeensuredthatallnational
regulations with regard to chimney
systemsareobserved.
Notes
Thetablesbelowgiveguidanceon
themaximumlengthsofairandue
gastubesthatmaybeconnected.Ifa
roomsealedinstallationisbeingmade
utilisingseparateairandue
gastubes,thelengthsofbothtubes
mustbeaddedtogetherandnot
exceed the relevant value given in the
tables.
Theradiusofanybendusedintheue
gassystemmustnotexceed87.5°.
Walls that are sensitive to heat
should be insulated.
Construct the ue system in such
way that no recirculation may take
place.
Installation
Connections
Air- / ue gas ducts for individual boilers
Allboilermodelshaveaparallelue
connection.
It is not necessary to install a separate
condensatedrainfortheuegas
system,sincethecondensatewillbe
ushedoutviatheboilerandintothe
siphon.Pleaseobservethefollowing
recommendations:
- Only use corrosion-resistant
material
- Thediametermustbecalculated
and selected according to the
national regulations.
- Thelengthoftheuegassystem
mustbekeptasshortaspossible
(and must not exceed the
maximum permitted length, see the
documentation for planners)
- Horizontaluegastubesmusthave
aninclinationofatleast3°back
towardstheboiler.
Air supply connection
If required, a separate room sealed
airsupplytubemaybeconnected
via the inclusion of the optional air
supplyconnectortting.Thediameter
mustbecalculatedinconformitywith
nationalregulationsandincombination
withtheuegasgassystem.The
overall resistance of the air supply
anduegastubesmaynotexceed
the maximum supply pressure of the
Fan at any time. (Also see the Chapter
“Technical data”)
Dimensioning (reference value)
Required minimum (ue enclosure) shaft cross-section
Diameterueduct Square shafts Round shafts
100 mm 140 x 140 mm 160 mm
Øtubes(openorparalleltubes
room sealed installation)
Maximum length in metres
Changes of direction 0 2 3 4
60
Ø100 mm
82 78 76 74
70 60 56 54 52
100 34 30 28 26
120 20 16 14 12
140 16 12 10 8
170
Ø130 mm
35 30 27 25
200 30 25 22 20
Øtubes(concentricroomsealed
installations)
Maximum length in metres
Changes of direction 0 2 3 4
60
Ø100/150 mm
34 30 28 26
70 23 19 17 15
100 13 9 7 5
120 10 6 4 2
140 8 5 3 1

Table of Contents

Related product manuals