EasyManua.ls Logo

Elcon HiD 2000 Series - Hid 2822;2824

Default Icon
129 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-11
6.2.9 HiD 2822/2824
For these isolators, the input/output relationship is configurable. Two distinct check procedures are therefore
presented. For simplicity, the "fault detection disabled" mode is not covered by the procedure.
Input closed / relay output de-energised configuration:
a) for HiD 2822, set the configuration switches as: S1=ON, S2=ON, S3=ON, S4=ON
for HiD 2824, set the configuration switches as: S1=ON, S2=ON, S3=ON, S4=ON, S5=ON, S6=ON, S7=ON, S8=ON;
b) connect the power supply at the termination board supply terminals; connect the resistor box Rc at the input
terminals; connect the first multimeter R1 (resistance mode) at the output terminal; connect the second multimeter
R2 (resistance mode) at the second output terminal only for model HiD 2822; set the supply at 24 V and switch it
on; the green power LED must go on;
c) set the resistor box to 1 K; both the yellow status and the red fault LED must be off; both multimeters (HiD
2822) or the tested channel multimeter (HiD 2824) must give a "open circuit" reading;
d) set the resistor box to 10 K; the yellow status LED must be on and the red fault LED must be off; both
multimeters (HiD 2822) or the tested channel multimeter (HiD 2824) must give an "short circuit" reading;
e) set the resistor box to 0 (input short-circuit); the yellow status LED must be off and the red fault LED must be
on; both multimeters (HiD 2822) or the tested channel multimeter (HiD 2824) must give an "open circuit" reading;
f) disconnect the resistor box (input open-circuit); the yellow status LED must be off and the red fault LED must be
on; both multimeters (HiD 2822) or the tested channel multimeter (HiD 2824) must give an "open circuit" reading;

Table of Contents