Rosemount Model 8800C Vortex Flowmeter
A-14
Canadian Standards Association (CSA) Approvals
E6 Explosion-proof for
Class I, Division 1, Groups B, C, and D;
Dust-Ignition proof for
Class II, Division 1, Groups E, F, and G;
Class III, Division 1
Hazardous locations;
Class I, Division 2, Groups A, B, C, and D;
factory sealed
I6 Intrinsically safe for
Class I, Division 1, Groups A, B, C, and D;
Intrinsic safety approval only when connected in accordance
with Rosemount drawing 08800-0111;
temperature code T3C (see Table A-6)
C6 E6 and I6 combination (see Table A-6)
Table A-6. CSA Entity Approvals
Barrier Manufacturer/Model
CSA Approved for Class I,
Division 1, Groups
A B C D
Any CSA approved zener barrier
30 V,
330 or
28 V,
300 or
25 V,
200 or
22 V,
180
••••
Foxboro Converters
2AI-12V-CGB, 2AI-13V-CGB
2AS-I3I-CGB, 3A2-I2D-CGB
3A2-I3D-CGB, 3AD-I3I-CGB
3A4-I2D-CGB, 2AS-I2I-CGB
3F4-I2DA
NA • • •
Any CSA approved zener barrier
30 V,
150
NA NA ••