SEP 2005 MODEL 1000
INSTALLATION AND SETUP
3-84
Figure 3-36. Digital Input Jumper Wire Connections.
(4) For digital input signals, also make these "jumper-wire" connections (see Figure 3-36):
(a) Jumper terminals #4 and #6 (common) on "J7".
(b) To enable digital input, apply to terminal #5, on "J7", either 12 or 24 volts DC:
- 12 volts is DC available from the GC Controller's power supply by jumpering
terminal #2 to terminal #5 (see NOTE, below, and Figure 3-36).
- 24 volts DC is not available from the GC Controller's power supply; it must
be obtained from an external power supply.