MODEL 1000 SEP 2005
INSTALLATION AND SETUP
3-27
3.3.2 Analyzer Ac-power Wiring
1
Observe Precautions and Warnings
2
Plan Site Location
3
Obtain Supplies and Tools
4
Install Analyzer Wiring
»
To connect 115 volts AC-Power to the Analyzer, follow these steps:
(1) Locate the three leads for connecting 115 volts AC-power to the Analyzer.
(a) Leads are "pig-tailed" from the Analyzer power supply through conduit to a customer
power NPT connection at the top of the Analyzer stack.
(b) Leads are colored as follows:
- HOT black
- NEUTRAL white
- GROUND green
(2) Connect Analyzer AC-power leads to properly controlled 115 volts AC-power source (i.e.,
with circuit breaker and power disconnect switch).
SERIOUS PERSONAL INJURY OR DEATH POSSIBLE
Do not connect AC power leads without first ensuring that AC power source is switched
OFF.
Failure to observe all safety precautions could result in serious injury or death.
(a) Make power line splices and conduit seals that comply with applicable wiring
requirements (for hazardous environments).