Table 6-5: Warning Message Descriptions (continued)
Message Description Action
Map conflict tank no. Input register no. 6260
Check that tank measurement
variables are mapped to the
right source parameters:
1. In TankMaster Winsetup,
right-click the ATD device
icon associated with the
current tank.
2. Click the Properties
option.
3. In the 22XX ATDwindow
select the Advanced
Parameter Source
Configuration tab.
Contact Emerson Automation
Solutions/Rosemount Tank
Gauging service department.
Map conflict TMV type
(TMV=Tank Measurement
Variable)
Input register no. 6262
0: TMV Level
1: TMV Ullage
2: TMV Level Rate
3: TMV Signal Strength
4: TMV Free Water Level
5: TMV Vapor Pressure
6: TMV Liquid Pressure
7: TMV Air Pressure
8: TMV Ambient Temperature
9: TMV Vapor Avg Temperature
10: TMV Liquid Avg
Temperature
11: TMV Tank Avg Temperature
12-27: TMV Temp1 - TMV
Temp 16
50: TMV Observed Density
51: TMV Reference Density
52: TMV Flow Rate
53: TMV Tank Volume
54: TMV Tank Height
55: TMV Middle Pressure
56: TMV Delta Level
60-64: TMV USER DEF 1 - 5
Map conflict device 1
Input register no. 6264
Map conflict device 1 TV no.
(TV=Tank Variable)
Input register no. 6266
TV number 0 - 1019 (Level,
Ullage, Level Rate, Signal
Strength etc.)
Map conflict device 2 Input register no. 6268
Map conflict device 2 TV no.
(TV=Tank Variable)
Input register no. 6270
TV number 0 - 1019 (Level,
Ullage, Level Rate, Signal
Strength etc.)
Internal map conflict Input register no. 6272
Bit 1: TMV Vapor average
temperature
Bit 2: TMV Liquid average
temperature
Bit 3: TMV Tank average
temperature
Bit 4: TMV Observed Density
Reference Manual Service and troubleshooting
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 109