Message Description Action
Bit 5: TMV Reference Density
Bit 6: TMV Tank Volume
Bit 7: Mult TV Map
Bit 8: TMV Internal Map
Bit 9: TMV Arithmetic Value
6.3.3 Error messages
Error messages may be displayed on the Rosemount 2410 integral display and in the
Rosemount Tankmaster program. You also have the option to view Input Register 1002
for an overview of active device errors (see View and configure diagnostic registers using
TankMaster
™
or Viewing input and holding registers using TankMaster
™
for information on
how to view diagnostics and various Input registers with TankMaster WinSetup).
For each error message that may appear in Input register 1002, detailed information can
be found in Input registers 6100 to 6124 as shown in Table 6-6.
Table 6-6: Error Message Descriptions
Message Description Action
RAM error Input register no. 6100.
A gauge data memory (RAM)
error has been detected during
the startup tests. Note: this
automatically resets the gauge.
Contact Emerson Automation
Solutions/Rosemount Tank
Gauging service department.
FPROM error Input register no. 6102:
Bit 0: checksum
Bit 1: Application version
Bit 2: Application checksum
Probably a checksum error in
the application software. Try to
reprogram the Rosemount
2410.
HREG error Input register no. 6104:
Bit 0: Checksum
Bit 1: Limit
Bit 2: Version
Bit 3: Read
Bit 4: Write
Probably a checksum error
caused by power failure
between a configuration
change and CRC update. Reset
to factory configuration (see
Loading the default database
using TankMaster
™
) and
reconfigure the Rosemount
2410. Use the Reset command
before checking the error
status.