Table 6-6: Error Message Descriptions (continued)
Message Description Action
SW error Input register no. 6106:
Bit 0: Undefined SW Error
Bit 1: Task Not Running
Bit 2: Out of stack space
Bit 3: Unused RAM access
Bit 4: Divide by zero
Bit 5: Reset Counter Overflow
Bit 15: Simulated SW Error
The Rosemount 2410 software
is having trouble running
stable.
1. Switch off the power to
the tank hub for at least
one minute.
2. Switch power on again.
If the problem persists, contact
Emerson Automation
Solutions/Rosemount Tank
Gauging service department.
Other Memory Error Input register no. 6108:
Bit 0: CheckSum
Bit 1: Stack
Contact Emerson Automation
Solutions/Rosemount Tank
Gauging service department
Sys Error Input register no. 6110.
Bit 0: Task Supervisor
Display Error Input register no. 6112.
Bit 0: Hardware
Bit 1: Com
Bit 2: Configuration
Aux Error Input register no. 6114.
Bit 0: Internal temperature out
of limits
Bit 1: Internal temp
measurement failed
Bit 2: Internal temperature
device failed
Bit 3: Relay 1
Bit 4: Relay 2
Bit 5: Power
FF Stack Error Input register no. 6116.
Tankbus Communication Error Input register no. 6118.
Bit 0: Unknown device
connected to the Tankbus
Host Communication Error Input register no. 6120.
Bit 1: Hardware Primary
modem
Bit 2: Hardware Secondary
modem
Bit 3: Illegal Primary modem
Bit 4: Illegal Secondary modem
Reference Manual Service and troubleshooting
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 111