Table A-2: Fieldbus Combination Matrix (SIL)
Primary Fieldbus options
TRL2 RS485 Enraf Analog out
passive (non-IS)
Analog In
passive
(non-IS)
Secondary Fieldbus
options
Code R 4 E B 7
TRL2 R SIL 2 (relay) SIL 2 (relay) No No No
Enraf E SIL 2 (relay) SIL 2 (relay) No No No
WirelessHART W SIL 2 (relay) SIL 2 (relay) or
SIL 3 (relay)
SIL 2 (relay) SIL 2 (4-20 mA
and/or relay)
SIL 2 (relay)
L&J Tankway 1500
XL/MCG 2000
L SIL 2 (relay) SIL 2 (relay) No No No
Varec Mark/Space GT
1800/1900
V SIL 2 (relay) SIL 2 (relay) No No No
Whessoe WM 550/660
(digital current loop)
H SIL 2 (relay) SIL 2 (relay) No No No
GPE 31422/31423 (digital
current loop)
G SIL 2 (relay) SIL 2 (relay) No No No
Sakura MDP/V1 U SIL 2 (relay) SIL 2 (relay) No No No
Tokyo Keiso T SIL 2 (relay) SIL 2 (relay) No No No
Analog out active (IS) C SIL 2 (4-20 mA
and/or relay)
SIL 2 (relay) or
SIL 3 (relay)
SIL 2 (4-20
mA and/or
relay)
No No
Analog out active (non-IS) A SIL 2 (4-20 mA
and/or relay)
SIL 2 (4-20 mA
and/or relay)
SIL 2 (4-20
mA and/or
relay)
No No
Analog out passive (IS) D SIL 2 (4-20 mA
and/or relay)
SIL 2 (relay) or
SIL 3 (relay)
SIL 2 (4-20
mA and/or
relay)
No No
Analog out passive (non-
IS)
B SIL 2 (4-20 mA
and/or relay)
SIL 2 (4-20 mA
and/or relay)
SIL 2 (4-20
mA and/or
relay)
No No
Analog in active (IS) 8 SIL 2 (relay) SIL 2 (relay) or
SIL 3 (relay)
SIL 2 (relay) No No
Analog in active (non-IS) 6 SIL 2 (relay) SIL 2 (relay) SIL 2 (relay) No No
Analog in passive (IS) 9 SIL 2 (relay) SIL 2 (relay) or
SIL 3 (relay)
SIL 2 (relay) No No
Analog in passive (non-IS) 7 SIL 2 (relay) SIL 2 (relay) SIL 2 (relay) No No
None 0 SIL 2 (relay) or
SIL 3 (relay)
SIL 2 (relay) or
SIL 3 (relay)
SIL 2 (relay) or
SIL 3 (relay)
No No
Reference Manual Specifications and reference data
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 121