Markings
Entity HART
active
When b = Tank Bus (Fieldbus - Power and Communication): E and when
d = Secondary Communication Bus (HART
®
/4-20mA Active IS Input/
Output): W, C or 8: ENTITY IS POWER SUPPLY XP CL I, DIV 1 GPS C, D &
Associated Apparatus providing IS circuit to CL I, DIV 1, GPS C & D; DIP
CL II/III, DIV. 1, GP E, F & G; CL I, ZONE 1 Ex db eb [ib] IIB ENTITY IS I/O
ACTIVE: XP CL I, DIV 1 GPS C, D & Associated Apparatus providing IS
circuit to CL I, DIV 1, GPS C & D ACTIVE: CL I, ZONE 0 Ex db eb [ia IIC] IIB
Amb. Temp. Limits -50°C to +70°C Temp. Class T4 SEE CONTROL
DRAWING D7000002-611 Type 4X; IP66/67
Markings
Entity HART
passive
When b = Tank Bus (Fieldbus - Power and Communication): E and when
d = Secondary Communication Bus (HART
®
/4-20mA Passive IS Input/
Output): D or 9: ENTITY IS POWER SUPPLY XP CL I, DIV 1 GPS C, D &
Associated Apparatus providing IS circuit to CL I, DIV 1, GPS C & D; DIP
CL II/III, DIV. 1, GP E, F & G; CL I, ZONE 1 Ex db eb [ib] IIB ENTITY IS I/O
PASSIVE: CL I, ZONE 1 Ex db eb ib IIB Amb. Temp. Limits -50°C to +70°C
Temp. Class T4 SEE CONTROL DRAWING D7000002-611 Type 4X;
IP66/67
Ex marking Comm. Bus Ui
V
Ii
mA
Pi
W
Ci
µF
Li
mH
Uo
V
Io
mA
Po
W
Co
µF
Lo
mH
Group
Ex db eb [ib] IIB T4 FISCO - - - - - 15 354 5.32 - - IIB
Ex db eb [ia IIC] IIB
T4
HART/4-20mA
Active
- - - - - 23.1 95.3 0.55 0.14 3.9 IIC
1.0 15 IIB
3.67 33 IIA
Ex db eb ib IIB T4 HART/4-20mA
Passive
30 300 1 0 0 - - - - - IIB
Ex db eb [ib] IIB T4 Fieldbus - - - - - 15 200 3 1.99 143 IIB
Special Conditions for Safe Use (X):
1. The flamepaths of the equipment are not intended to be repaired. Consult the
manufacturer if repair of the flamepath joints is necessary.
Reference Manual Product certifications
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 139