2. In the 2410 Tank Hub Device Live List, identify the Analog Input device.
The Analog Input appears as Device Type=Analog Input.
3. In the TankMaster WinSetup workspace, right-click the Rosemount 2410 Tank Hub
icon and choose the Properties option.
4. Select the Tank Database tab.
5. Associate the Analog Input with a tank in the tank hub’s tank database and click the
Apply button.
Need help?
See the Rosemount Tank Gauging System Configuration Manual (Document no.
00809-0300-5100) for more information on how to configure the tank database.
6. Select the Device Tags tab and click the Install New Devices in TankMaster button.
Now the Analog Input will be installed as an ATD in the TankMaster WinSetup
workspace. Note that although the analog input is actually connected to the
Rosemount 2410 Tank Hub, it is handled as an ATD.
Reference Manual Advanced configuration
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 183