C.10.2 HART slave configuration
The Rosemount 2410 Tank Hub can act as HART Master for up to three HART slaves in
multi-drop configuration. Current mode 4-20 mA is supported in case only one HART
device is connected.
Procedure
1. Identify the HART Slave in the Rosemount 2410 Tank Hub Device Live List.
It will appear as “HART” in the column named “Connected via”.
2. Open the Rosemount 2410 tank database and locate the device which will act as a
HART Slave.
3. Associate the HART slave with a tank position in the Rosemount 2410 tank database
and click the Apply button.
4. Select the Device Tags tab and click the Install New Devices in TankMaster button.
Now the HART Slave device will be installed as an Auxiliary Tank Device (ATD) in the
TankMaster WinSetup workspace. Note that although the HART device is actually
connected to the Rosemount 2410, it is handled as an ATD in TankMaster.
5. In the TankMaster WinSetup workspace, right-click the ATD device icon and choose
Properties.
6. Select the Advanced Parameter Source Configuration tab.
7. Select the desired check box to enable mapping of tank measurement variable to
source device and parameter.
8. Choose the desired tank parameter and value unit.
Reference Manual Advanced configuration
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 187