Example
Vapor Pressure is selected in this example.
9. In Source Device Type / ID / No list, select the appropriate HART device.
Example
In the example above, a 3051 PT is selected.
10. Choose the appropriate source parameter; Hart PV, Hart SV, Hart TV, or Hart QV.
11. In case there are more HART slaves connected, repeat Step 4 to Step 7.
12. In TankMaster WinSetup, install and configure the tank that the HART Slave device
was associated with in the Rosemount 2410 tank database (see step Step 3).
13. Verify that the tank parameter receives measurement data from the HART Slave by,
for example, opening the Tank View window in TankMaster WinOpi.
C.10.3
HART slave mapping
In case a Rosemount 2240 Multi-Input Temperature Transmitter is used, some parameters
can not be mapped manually to a HART Slave as described in section HART slave
configuration. See Table C-6 for a list of parameters that can be mapped.