Conductor recommendations
Ensure that you use cables suitable for the terminal block of the Rosemount 2410. The
terminal block is designed for cables that meet the specifications as illustrated in Figure
3-15.
Figure 3-15: Conductor and Insulation Requirements
A. Stripping length: 10 mm
B. Conductor cross-sectional area, see Table 3-7
Table 3-7: Terminal Connection for Details for End User
Type Rated (V) Rated (A) Strip
length
(mm)
Solid wire
size (mm
2
)
Stranded
wire size
(mm
2
)
Flexible
wire size
(mm
2
)
Clamping
range
(mm
2
)
Resistance
(MΩ)
ZDUB
2.5-2/2AN
550 21 10 0.5 - 4 0.5 - 2.5 0.5 - 2.5 0.13 - 4 1.33
ZDUB
2.5-2/4AN
550 21 10 0.5 - 4 0.5 - 2.5 0.5 - 2.5 0.13 - 4 1.33
No other wire sizes or types than the ones specified in instructions must be used. The
terminal blocks must either be mounted next to another block of the same type and size
or with an end plate.
Manually cut cross connections and cross connections with blank ends [ZQV’s >=20 poles)
shall not be used.