b) Select Install new.
3. Choose device type 2460 System Hub.
4. Specify a name tag in the 2460 System Hub Tag input field.
This tag will be used as an identifier of the system hub in various windows and
dialogs.
5. Click the Next button to proceed with the installation wizard.
6. Verify communication with the host computer/TankMaster PC.
7. Verify that Host ports and Field ports are properly configured.
Host ports are used for communication with TankMaster work stations or other
host systems. Field ports are used for communication with field devices such as the
Rosemount 2410 Tank Hub, the Rosemount 5900S Radar Level Gauge, and others.
8. Configure the tank database. Ensure that Modbus Addresses of the connected
devices are properly set. These addresses must correspond to the Rosemount 2410
Tank Hub database settings.
Need help?
See the Rosemount 2460 System Hub Reference Manual for more information on how to
setup the Rosemount 2460 System Hub.
Configuration Reference Manual
December 2019 00809-0100-2410