6.2.11 Testing the relays using TankMaster
The Manual Control of Relay function lets you manually open or close the Rosemount
2410 Tank Hub built-in relays in order to verify the relay function. After the specified
Safety Reset Time the relay automatically returns to normal mode. To change relay state
by using the TankMaster WinSetup program do the following:
Procedure
1. In the TankMaster WinSetup workspace, select the Rosemount 2410 icon.
2. Right-click and select Manual Control Relay.
3. Select the virtual relay functions to be tested; Virtual Relay 1, Virtual Relay 2, etc.
Up to ten virtual relay functions can be configured for a Rosemount 2410 Tank Hub.
4. Specify a Safety Reset Time.
This value specifies the time period for the relay to stay in the test state. When the
specified period of time has elapsed, the relay automatically returns to the original
state. The relay will reset even if communication with the TankMaster PC would fail.
5. Choose the desired Manual Relay State. Available options are:
Alarm
Normal
Toggle
6. Click the Set button.
Now the selected relay changes state for the specified number of seconds and then
returns to the previous state.
Related information
Configure a virtual relay output
Reference Manual Service and troubleshooting
00809-0100-2410 December 2019
Rosemount 2410 Tank Hub 93