5-6 • Site Supervisor Controller User Guide 2.0  026-1800 Rev 3 02-AUG-2016
whether the Count is reset based on the logic level, the 
rising edge or the falling edge. The counter increments 
based on the digital output after the bypass block.
The PRI DEMAND SHED input provides a way to 
have the cell shut down in demand shed situations. If the 
PRI DEMAND SHED is ON, the output will be set to the 
logical OFF position by using the bypass functionality. 
The Cmd When Off param will set the proper off value for 
the output. The counter will not increment when in 
demand shed regardless of the inputs.
5.3.2 Command Alarming
The command value will be used to determine the 
alarm state. The command value is the combined value of 
all the digital inputs of the cell, plus occupancy, and 
schedules.
When the command value changes to alarm condition, 
the delay timer will start. If the state changes, the timer 
will stop and no alarm will be issued. If the state stays for 
the duration of the timer, an advisory will be issued. If a 
state change occurs to the opposite state after the advisory 
has been issued, it will be returned to normal.
If the advisory is reset, and the alarm/notice condition 
still exists, the delay period will be honored. Advisories 
will return to normal if the command value stays in the 
non-alarm/notice condition for the duration of the clear 
delay. If the command value changes back to the alarm 
condition, during the clear timer, the advisory will not 
return to normal.
5.3.3 Alarm Output When On/Off 
Parameters
Alarm When On redefines the definition of the 
command “ON” as it relates to the state of the command 
output. When the Sensor Control application calls for the 
output to be “ON,” the command output will switch to the 
state selected in the Cmd When On parameter. Select 
either ON, OFF, or NotAct in this field.
5.3.4 Control Bypass
The digital output may be bypassed with a timed 
bypass. The output by be bypassed to ON, OFF or NONE. 
Once the STRT TIMED BYP goes high, the bypass 
remains in effect until the Bypass Time has expired. The 
CNCL TIMED BYP will cancel any bypass and operation 
will return to normal. If STRT TIMED BYP is still on, it 
must go low for one update before it will activate another 
bypass.
5.4 Lighting Control
The Lighting Control application controls indoor and 
outdoor lights. The number of Lighting Applications 
allowed is based on the total number of applications 
allowed in the controller. Additional applications (more 
than 24) may be added with a separate license key.
5.4.1 Lighting Control Logic
The user can specify the combination of inputs 
required to turn the lights on and a different combination 
of inputs to turn the lights off. The four inputs that may be 
combined are:
1. Digital Input - The digital input includes: Light 
Level Sensor Input, Logic Input, Schedule Input 
and Solar Input.
2. Light Level Sensor - If Light Level and Solar are 
used together, Light level sensor checking will be 
enabled if light level proof is enabled. If the Light 
Level Sensor and Solar Calculation do not match 
for a user-specified time delay, an alarm will be 
generated. This alarm will be submitted to the 
alarm subsystem. The text of the alarm will be 
“Light Level Sensor - Possible Failure”.
3. Schedule - The controller's Lighting Application 
will not provide an internal schedule capability. 
An external time schedule application is required 
to control the lighting output based on a schedule.
4. Solar (Sunrise/Sunset) - If Light Level and 
Solar are used together, Light Level sensor 
checking will be enabled if Light Level Proof is 
enabled. If the Light Level Sensor and Solar 
Calculation do not match for a user-specified 
time delay, an alarm will be generated. This 
alarm will be submitted to the alarm subsystem. 
The text of the alarm will be “Light Level Sensor 
- Possible Failure”.
The following parameters are provided by the 
application to configure the logic for turning the light 
output on or off.
• Input 1 - Chooses the type of input value that is 
used as the first value in the logical equation. 
Choose Logic, Sched, Llev, or Solar.
• Logic 1 - Chooses the method of combining Input 
Source 1 with Input Source 2 (AND or OR). If you 
NOTE: the View Lighting application status 
events can be viewed from the device Status 
screen.