5-42 • Site Supervisor Controller User Guide 2.0  026-1800 Rev 3 02-AUG-2016
5.27.3 Refrigeration Control
5.27.3.1 EEVs (Liquid Pulse and Liquid 
Stepper)
In CC-100P, CC-100LS, EC2, and CCB (liquid and 
pulse stepper) case controllers, there are two different con-
trol systems that work together to regulate refrigeration: 
temperature control and superheat control.
Temperature Control
Temperature Control measures the case temperature 
and turns refrigeration ON or OFF as required to keep the 
case within a certain proximity of the user-specified tem-
perature setpoint. 
The user supplies Temperature Control with the set-
point and a deadband, which is the range of case tempera-
tures equally above and below the setpoint within which 
the case temperature will be considered acceptable. When 
the case temperature is above the setpoint plus
 one-half the 
deadband, refrigeration will be turned ON. It will remain 
ON until the temperature drops to below the temperature 
setpoint minus
 one-half the deadband, at which point 
refrigerant flow will be turned OFF.
Case temperature may be supplied to Temperature 
Control by a supply air sensor, a return air sensor, or a 
mixture of both the supply and return air sensor values.
Temperature Control itself does not vary the opening 
percentage of the pulse or stepper valve; it simply 
addresses the case’s need for refrigerant flow to maintain 
its setpoint. Once refrigeration is started, control of the 
valve is handled by Superheat Control.
Superheat Control
The difference between the temperature of the refriger-
ant going in to the evaporator inlet (the coil in tempera-
ture) and the refrigerant leaving the evaporator outlet (the 
coil out temperature) is called Superheat. When refriger-
ant is flowing through an evaporator, Superheat Control 
uses PID Control to keep the Superheat at a user-defined 
Superheat setpoint. Superheat Control positions the valve 
to increase or decrease refrigerant flow in an effort to keep 
the Superheat equal to a user-defined Superheat setpoint.
Recovery Mode
Recovery Mode is a special part of Superheat Control 
that occurs at the beginning of every refrigeration cycle. 
When refrigeration has been OFF and Temperature Con-
trol calls for refrigeration to be ON, a Recovery Mode 
begins, during which the valve is fixed to a user-defined 
percentage (usually 70%) for a fixed amount of time. This 
floods the previously empty evaporator with refrigerant 
and gradually establishes a differential between the coil in 
and coil out temperatures. When the Recovery Mode ends, 
the superheat will be relatively close to the setpoint; at this 
time, Superheat Control will begin.
Recovery Mode always lasts for a specific number of 
seconds. The case controller determines the duration based 
on past performance of the evaporator during previous 
Recovery Modes.
Thermostatic Expansion Valves (TXVs)
As an alternative to regulating superheat using EEVs, 
case controllers also support cases that use mechanical 
thermostatic expansion valves (TXVs). When TXVs are 
being used, the case controllers use only Temperature 
Control to turn refrigeration ON and OFF. Superheat 
Control is disabled, since it is assumed the TXV is tak-
ing care of the superheat.
5.27.3.2 EEPRs (Suction Stepper)
The CC-100H, CS-100, and CCB (suction stepper and 
lineup) control case temperature from the suction side of 
the evaporator by using an EEPR to regulate suction pres-
sure. 
Suction-side control differs from liquid-side control in 
that Superheat Control is not used. In liquid-side control, 
the valve aperture is controlled in order to achieve a super-
heat setpoint. In suction-side control, the CC-100 changes 
the valve aperture to achieve the case temperature set-
point.
Case temperature may be supplied by a supply air sen-
sor, return air sensor, or a mixture of the two values.
Temperature Control uses PID control to operate the 
valve and keep the case temperature input value equal to 
the case temperature setpoint.
Recovery Mode
Recovery Mode for suction-side case controllers is 
slightly different than Recovery Mode for liquid-side 
controllers. Suction-side case controllers enter Recovery 
Mode only after a defrost or cleaning cycle, and it does 
so in order to bring the case temperature down to a level 
that is controllable by Temperature Control.
During Recovery Mode, the valve is opened to a fixed 
percentage until the case temperature falls below the 
case setpoint. When this occurs, the case controller exits 
Recovery Mode and begins normal Temperature Con-
trol.
5.27.4  Defrost Control
The physical aspects of defrost control, such as shut-
ting off valves and turning on defrost heat sources, is han-
dled by the case controller. When operating on its own, a 
case controller initiates defrost cycles at programmed time 
intervals. When connected to a Case Circuit application, 
the case controllers’ defrost times are coordinated and 
scheduled by the Site Supervisor.