HVAC Control Software Overview • 5-13
• Fan Proof Fail - When fan proof failure is 
detected, heating and cooling loads are shut down 
until the proof failure goes away or the fan proof 
alarm is reset or cleared. If the fan is configured to 
shut down on a fan proof failure, the system is 
restarted by setting the FAN FAIL RST input to ON 
or clearing the fan proof failure from the advisory 
log.
• SHUTDOWN input is ON - The application goes 
into a shutdown mode that turns off the fan. The fan 
remains OFF as long as the SHUTDOWN input is 
ON.
Control Temperature above Economization Setpoint
If the control temperature is greater than the occupied 
cooling setpoint minus the occupied economization delta, 
then economization is permitted. If the control 
temperature is greater than the unoccupied cooling 
setpoint minus the unoccupied economization delta, then 
economization is permitted. If the either the control 
temperature or the setpoint minus the economization delta 
has a value of NONE, then economization is not 
permitted.
Low Supply Temp Lockout
If the supply temperature is below “Econ Lock Temp”, 
the economizer is disabled.
5.6.14 Determine the Analog 
Damper Position
The analog damper position is determined by using a 
PID loop. The output is based on the mixed air 
temperature compared to the occupied or unoccupied 
mixed air setpoint (“Occ CL Mix Temp” or “Unoc CL Mix 
Tmp”). The output is limited to the occupied or 
unoccupied minimum damper position. If the 
economization is inactive, the analog damper is set to the 
occupied or unoccupied minimum damper position, based 
on the current occupancy state. If the economization is 
active, the output from the Economizer PID loop is written 
to the analog damper output.
5.6.15 Determine the Digital 
Damper Position
The digital damper output turns ON when 
economization is active.
5.6.16 Heat Pump Control
If any heat pump stages are defined, they activate in 
parallel with the first cooling and heating stages defined. 
For example, if one heat pump stage and one heat stage are 
defined, when a call for heat occurs, the heat pump stage is 
considered stage one and it turns on along with the heat 
stage (HEAT STAGE 1). If a second stage of heat is 
required, two heat stages should be defined. Likewise, for 
cooling, if one heat pump stage and one standard cooling 
stage are defined, and a call for cooling occurs, the heat 
pump stage is considered cool stage one and it turns on 
along with the COOL STAGE 1 output. If a second stage 
of cooling is required (not a heat pump stage), two cool 
stages should be defined.
5.6.17 Reversing Valve
The reversing valve must be identified as either a 
heating or cooling reversing valve by setting the 
“Reversing Valve” parameter. When the reversing valve is 
set to cooling, the reversing valve turns on when a call for 
cooling is active and turns off when a call for heating is 
active. Likewise, when the reversing valve is set to 
heating, the reversing valve turns on when a call for 
heating is active and turns off when a call for cooling is 
active. Once the call for heating or cooling is no longer 
active, the reversing valve remains in its last known state. 
When the AHU application is reset, the reversing valve 
output initializes the OFF state.
5.6.18 Compressor Output
When either a call for heating or cooling is active, the 
compressor output for the called stage turns on. When the 
heating or cooling call is no longer active, the compressor 
turns off.
Control Temperature
A control temperature advisory occurs after a user-
specified time delay for both high and low temperature 
conditions. This advisory must have associated parameters 
to allow the user to specify the high and low advisory 
value and the delay, and must be separate setpoints for 
occupied and unoccupied mode.
Supply Fan Proof Failure
A supply fan proof failure advisory is generated when 
the AHU is calling for the supply fan to be ON and the fan 
status input indicates the fan is not operating. This 
advisory should have an associated parameter to allow the 
user to enable or disable the advisory and a parameter to 
specify the time delay before the advisory is activated.
5.6.19 Curtailment
To set up curtailment in the system software, the user 
must designate which specific heating and cooling stages 
is subject to curtailment. When the power company sends 
a curtail command (for example, the value of the 
curtailment device switches to “CLOSED”), all stages that 
are set up to be curtailed is shut off and locked out.