Accessories Gammapilot FMG50
100 Endress+Hauser
10.3.3 Use
Permitted
Not recommended, observe mounting instructions
A0037727
A Level measurement, FMG50
B Point level measurement, FMG50
C Such horizontal mounting is not recommended
1 Retainer for pipe diameter 80 mm (3.15 in)
2 Retainer for pipe diameter 95 mm (3.74 in)
3 Retaining bracket
Mounting instructions for horizontal mounting (see Figure C): The pipe must be
mounted by the customer. It is important to ensure that the installation clamping
power is sufficient to prevent the FMG50 from slipping. The dimensions are provided
in the "Dimensions of the mounting clamps" section.
L
CAUTION
Note the following when mounting the device
‣
The mounting device must be installed in such a way as to withstand the weight of the
Gammapilot FMG50 under all anticipated operating conditions.
‣
Four brackets must be used for measuring lengths of 1 600 mm (63 in) and more.
‣
To facilitate installation and commissioning, the Gammapilot FMG50 can be configured
and ordered with an additional support (order feature 620, option Q4: "Retaining
bracket").
‣
Clamping solution for pipe mounting must be provided by the customer on site
(see Figure C). Do not use the enclosed mounting clamps for a horizontal pipe. The
fixing bracket supplied can be used for FMG50.
‣
To prevent damage to the detector pipe of the Gammapilot FMG50, the maximum
torque that can be applied to tighten the retainer screws is 6 Nm (4.42 lbf ft).
10.4 Clamping device for density measurement FHG51
10.4.1 FHG51-A#1
For pipes with diameter 50 to 200 mm (2 to 8 in).
SD02543F