Commissioning Gammapilot FMG50
76 Endress+Hauser
1
2
Alarm
on
off
MaxSW
Zero/I
Span/II
Display
34
A0039285
1 Operating key for empty calibration (function I)
2 Operating key for full calibration (function II)
3 DIP switch for alarm current (SW-defined / Min alarm)
4 DIP switch for locking and unlocking the measuring device
Empty calibration: press and hold the operating key for empty calibration (I) > 3 s
Full calibration: press and hold the operating key for full calibration (II) > 3 s
Background calibration: simultaneously press and hold the operating key for empty
calibration (I) and the operating key for full calibration (II) > 3 s
Reset to factory defaults: simultaneously press and hold the operating key for empty
calibration (I) and full calibration (II) > 12 s. The LED starts flashing. When the flashing
stops, the device is reset to the factory default settings.
7.4.1 Level basic calibration
Calibration time per calibration: 5 min!
1. Reset
Press both keys > 12 s
2. Start background calibration
Press both keys > 3 s
The green LED is lit for one second and starts flashing at an interval of 2 s
3. Start empty calibration
Press the "Zero / 1" key > 3 s
The green LED is lit for one second and starts flashing at an interval of 2 s
Wait 5 min until the green LED stops flashing
4. Start full calibration
Press the "Span / 2" key > 3 s
The green LED is lit for one second and starts flashing at an interval of 2 s
Wait 5 min until the green LED stops flashing
A reset deletes all calibrations!
7.4.2 Status and power LED
A green LED that signals the status and button activation feedback is provided on the
electronic insert.
Behavior of the LED
The LED flashes once briefly when the measuring device is started
When a key is pressed, the LED flashes to confirm the key activation
When a reset is performed, the LED flashes as long as both keys are pressed and the
reset is not yet active (countdown). The LED stops flashing once the reset is active.
The LED flashes while calibration is being performed via onsite operation