Gammapilot FMG50 Commissioning
Endress+Hauser 47
7 Commissioning
7.1 Post-installation and post-connection check
Perform the post-installation check and the post-connection check for the FMG50 prior to
commissioning the measuring point.
Perform commissioning using the Commissioning Wizard!
If commissioning is performed via the menu, incorrect settings can result in device
failure.
7.2 Commissioning using the Commissioning Wizard
7.2.1 General information
When the device is switched on for the first time or following a reset to factory settings
(see Section 6.4), the device displays the error message F440 "Device is not calibrated",
the status signal indicates an alarm and the current output is set to failure current: MIN,
-10%, 3.6 mA (factory setting).
A Wizard is available in FieldCare, DeviceCare and the SmartBlue App to guide you
through the initial commissioning process.
FieldCare and DeviceCare are available for download. You need to register in the
Endress+Hauser software portal to download the application.
https://www.software-products.endress.com
SmartBlue enables operation via Bluetooth.
For details, see the "Commissioning via the SmartBlue App" section
The following diagrams show the display in FieldCare or DeviceCare. The displays in
other operating tools may differ, but the content is the same.
1. Connect the device with FieldCare, DeviceCare or SmartBlue App (Bluetooth).
2. Open the device in FieldCare, DeviceCare or SmartBlue App.
The dashboard (homepage) of the device is displayed:
A0039359
17 Screenshot: Commissioning Wizard
3. Click "Commissioning" to launch the Wizard.
4. Enter the appropriate value in each parameter or select the appropriate option. These
values are written directly to the device.
5. Click "Next" to go to the next page.