Description of device parameters (operating menu) Levelflex FMP51, FMP52, FMP54
124 Endress+Hauser
18.2.1 "Mapping" sequence
Confirm distance
Navigation
Setup ® Mapping ® Confirm distance
Description
Confirmation whether the measured distance matches the actual distance. Depending on the
selection, the device automatically determines the range over which the mapping will be
recorded.
Selection
• Manual map
To be selected if the range of mapping is to be defined manually in the Mapping end point
parameter. In this case it is not necessary to confirm the distance.
•
Distance ok
To be selected if the measured distance matches the actual distance. The device performs a
mapping and quits the sequence ("End of sequence" appears on the display).
• Distance unknown
To be selected if the actual distance is unknown. A mapping can not be performed and the
device quits the sequence ("End of sequence" appears on the display).
• Distance too small
To be selected if the measured distance is smaller than the actual distance. The device performs
a mapping and returns to the Confirm distance parameter. The distance is recalculated and
displayed. The comparison must be repeated until the displayed distance matches the actual
distance.
• Distance too big
To be selected if the measured distance is bigger than the actual distance. The device adjusts
the signal evaluation and returns to the Confirm distance parameter. The distance is
recalculated and displayed. The comparison must be repeated until the displayed distance
matches the actual distance.
• Tank empty
To be selected if the tank is completely empty. The device records a mapping covering the
complete length of the probe and quits the sequence ("End of sequence" appears on the
display).
• Delete all
To be selected if the present mapping curve (if one exists) is to be deleted. The device returns
to the Confirm distance parameter and a new mapping can be recorded.
Factory setting
Distance unknown
Additional information
For reference purposes the measured distance is displayed together with this parameter.
For interface measurements the distance always refers to the total level (not to the interface level).
If the teaching procedure Distance too small or Distance too big is quit before the
distance has been confirmed, a map is not recorded and the teaching procedure is reset after
60 s.
For FMP54 with gas phase compensation (product structure: feature 540 "Application
Package", option EF or EG) a map must NOT be recorded.
Mapping end point
Navigation
Setup ® Mapping ® Map. end point