Levelflex FMP51, FMP52, FMP54 Description of device parameters (operating menu)
Endress+Hauser 185
18.3.7 The "Device check" submenu
Start device check
Navigation
Diagnostics ® Device check ® Start device check
Description
Start of a device check.
Selection
No
No device check is performed.
Yes
A device check is performed.
If the error S941 "Echo lost" is present, a device check is not possible. First you have to
eliminte the cause of this error.
Factory setting
No
Result device check
Navigation
Diagnostics ® Device check ® Result device check
Description
Indicates the result of the device check.
Display
Installation ok
Accuracy reduced
A measurement is possible. However, the measuring accuracy may be reduced due to the signal
amplitudes.
Measurement capability reduced
A measurement is currently possible. Howerver, there is the risk of an echo loss. Check the
mounting position of the device and the dielectric constant of the medium.
Check not done
Last check time
Navigation
Diagnostics ® Device check ® Last check time
Description
Displays the operating time at which the last device check has been performed.
Additional information
Display format
Days (d), hours (h), minutes (m), seconds (s): 0000d00h00m00s