Levelflex FMP51, FMP52, FMP54 Description of device parameters (operating menu)
Endress+Hauser 125
Condition
Only visible if the Manual map option has been selected in the Confirm distance parameter.
Description
Definition of the distance up to which the mapping curve will be recorded.
Input range
0.1 m (0.33 ft) to length of probe (LN)
Factory setting
0.1 m (0.33 ft)
Additional information
The distance is measured from the reference point, i.e. from the lower edge of the mounting
flange or the threaded connection.
For reference purposes the Present mapping parameter is displayed together with this
parameter. Present mapping states up to which distance a mapping has already been recorded.
Record map
Navigation
Setup ® Mapping ® Record map
Conditions
Only visible if a value has been entered into the Mapping end point parameter.
Description
Starts the recording of the map.
Selection
• No
The map is not recorded. The device quits the sequence ("End of sequence" is displayed).
•
Record map
The map is recorded. When the recording is completed, the new measured distance and the
new mapping range appear on the display. These values must be confirmed by pressing Â. The
device quits the sequence. ("End of sequence" is displayed.)
• Delete all
The mapping (if one exists) is deleted and the device displays the recalculated measured
distance and the mapping range. These values must be confirmed by pressing Â. The device
quits the sequence. "End of sequence" is displayed.
Factory setting
No
18.2.2 "Advanced setup" submenu
Locking status
(® ä 113)
Access status display
(® ä 113)
Enter access code
Navigation
Setup ® Advanced setup ® Enter access code