Levelflex FMP51, FMP52, FMP54 Commissioning via operating menu (On-site display, FieldCare)
Endress+Hauser 81
Step Parameter Action Description
10
Setup ® Signal quality
Displays the signal quality of the level
echo.
(® ä 122)
11
Setup ® Mapping ® Confirm
distance
4)
Compare the displayed distance to the
real distance in order to start the
recording of the mapping curve.
(® ä 124)
1) only visible for devices with "interface measurement" application package
2)
only visible for coated probes and if "Tank type" = "Bypass/pipe"
3)
If required, lower DCs can be entered into "Setup ® Advanced Setup ® Level ® Medium property". However,
for DC<1.6 the measuring range may be reduced. For details please contact Endress+Hauser.
4) For FMP54 with gas phase compensation (product structure: feature 540 "Application Package", option EF or EG) a
map must NOT be recorded.
10.7 Configuration of an interface measurement
Only devices with the respective software option can be used for interface measurements.
This option is selected in the product structure: Feature 540 "Application package", option
EB "Interface measurement".
D
L
L
L
F
L
I
UP
D
I
LN
E
R
0%
100%
DK
(DC )
2 2
DK DC
1 1
( )
A0011177
å 29
Configuration parameters for interface measurements
R = Reference pioint of the measurement D
I
= Distance of interface (Distance from reference point to lower medium)
E = Empty calibration (= zero point) L
I
= Interface level
F = Full calibration (= span) D
L
= Distance from reference point R to total level
LN = Length of probe L
L
= total level
UP = Thickness of upper medium
Schritt Parameter Aktion Beschreibung
1
Setup ® Distance unit
Select distance unit.
(® ä 116)
2
Setup ® Operating mode
1)
Select "Interface".
(® ä 116)
3
Setup ® Tank type
Select tank type.
(® ä 117)
4
Setup ® Tube diameter
2)
Enter the diameter of the bypass or stilling well.
(® ä 117)