Levelflex FMP51, FMP52, FMP54 Integration into a PROFIBUS network
Endress+Hauser 75
9 Integration into a PROFIBUS network
9.1
Overview of the device database files (GSD)
Manufacturer ID 17 (0x11)
Ident number 0x1558
Profile version 3.02
GSD file Information and files under:
• www.endress.com
• www.profibus.org
GSD file version
9.2 Set device address
A0015686
å 23
Address switches in terminal compartment
9.2.1
Hardware adressing
1. Set switch 8 to "OFF".
2. Define the address with switches 1 to 7 according to the table below.
The address change becomes effective after 10 seconds. The device restarts automatically.
Switch 1 2 3 4 5 6 7
Value in position "ON"
1 2 4 8 16 32 64
Value in position "OFF"
0 0 0 0 0 0 0
2
98
3
4
5 6
7
8
1
DIP
ON
2 + 8 = 10
A0015902
å 24
Example of hardware addressing: switch 8 is in position "OFF"; switches 1 to 7 define the address.
9.2.2
Software addressing
1. Set switch 8 to "ON".
2. The device restarts automatically. The address remains the same as before (factory setting:
126).
3.
Set the required address via the operating menu: Setup ® Device address