Levelflex FMP51, FMP52, FMP54 Description of device parameters (operating menu)
Endress+Hauser 183
18.3.6 "Simulation" submenu
Assignment of measured variable
Navigation
Diagnostics ® Simulation ® Assign. meas. var.
Description
Use this function to select a process variable for the simulation process that is activated. The
display alternates between the measured value and a diagnostics message of the "function check"
category (C) while simulation is in progress:
The simulation value of the selected process variable is defined in the Value process
variable parameter (® ä 183).
Selection
• Off
•
Level
• Interface (for Operating mode = Interface)
• Interface thickness (for Operating mode = Interface)
• Level linearized
• Interface linearized (for Operating mode = Interface)
• Thickness linearized (for Operating mode = Interface)
Factory setting
Off
Value process variable
Navigation
Diagnostics ® Simulation ® Value proc. var.
Prerequisite
One of the following options is selected in the Assignment of measured variable parameter :
•
Level
• Interface
• Interface thickness
• Level linearized
• Interface linearized
• Thickness linearized
Description
Use this function to enter a simulation value for the selected process variable. Subsequent
measured value processing and the signal output use this simulation value. In this way, users can
verify whether the measuring device has been configured correctly.
Input range
Depends on the process variable selected
Factory setting
The current value of the selected process variable (at the moment the simulation is activated).
Switch output simulation
Navigation
Diagnostics ® Simulation ® Switch output simulation