Commissioning via operating menu (On-site display, FieldCare) Levelflex FMP51, FMP52, FMP54
82 Endress+Hauser
Schritt Parameter Aktion Beschreibung
5
Setup ® Tank level
Select tank level:
Partially filled (typical selection for measurements in
tanks)
Flooded (typical selection for measurements in bypasses)
(® ä 117)
6
Setup ® Distance upper
connection
For measurements in bypasses: Enter the distance from
the reference point R to the lower edge of the upper
connection.
Otherwise: Keep the factory setting.
(® ä 118)
7
Setup ® DC value
Enter dielectric constant of the upper medium.
(® ä 119)
8
Setup ® Empty calibration
Enter the distance E between the reference point R and the
minimum level (0%).
(® ä 119)
9
Setup ® Full calibration
Enter distance F between the minimum (0%) and maximum
(100%) level.
(® ä 120)
10
Setup ® Level
Displays the measured level L.
(® ä 120)
11
Setup ® Interface
Displays the interface height L
I
.
(® ä 121)
12
Setup ® Distance
Displays the distance D between the reference point R and
the level L.
(® ä 121)
13
Setup ® Interface distance
Displays the distance D
I
between the reference point R and
the interface L
I
.
(® ä 122)
14
Setup ® Signal quality
Displays the signal quality of the level echo.
(® ä 122)
15
Setup ® Mapping ® Confirm
distance
Compare the displayed distance to the real distance in order
to start the recording of the mapping curve.
(® ä 124)
1) only visible for devices with "interface measurement" application package
2)
only visible for coated probes and if "Tank type" = "Bypass/pipe"
10.8 Configuration of the on-site display
10.8.1
Factory settings of the on-site display for level measurements
Parameter Factory setting for devices with 1 current
output
Factory setting for devices with 2 current
outputs
Format display 1 value, max. size 1 value, max. size
Value 1 display Levele linearized Levele linearized
Value 2 display Distance Distance
Value 3 display Current output 1 Current output 1
Value 4 display None Current output 21
10.8.2 Factory settings of the on-site display for interface
measurements
Parameter Factory setting for devices with 1 current
output
Factory setting for devices with 2 current
outputs
Format display 1 value, max. size 1 value, max. size
Value 1 display Interface Interface
Value 2 display Level linearized Level linearized
Value 3 display Upper interface thickness Current output 1
Value 4 display Current output 1 Current output 2