Levelflex FMP51, FMP52, FMP54 Mounting
Endress+Hauser 33
J Coax probe (Feature 060)
LN Length of probe
R Reference point of the measurement
L M N
PEEK 7 mm (0.28 in)
Æ95 mm (3.74 in)
-
PFA 10 mm (3.94 in) 37 mm (1.46 in) 110 mm (4.33 in)
316L 4 mm (0.16 in)
Æ45 mm (1.77 in)
Æ75 mm (2.95 in)
-
6.2 Mounting requirements
6.2.1
Suitable mounting position
A
C
1
2 3
4
B
A0012606
Mounting distances
Distance (A) between wall and rod or rope probe:
for smooth metallic walls: > 50 mm (2")
for plastic walls: > 300 mm (12") mm to metallic parts outside the vessel
for concrete walls: > 500 mm (20") , otherwise the available measuring range may be
reduced.
Distance (B) between rod or rope probe and internal fittings in the vessel: > 300 mm (12")
Distance (C) from end of probe to bottom of the vessel:
Rope probe: > 150 mm (6 in)
Rod probe: > 10 mm (0.4 in)
Coax probe: > 10 mm (0.4 in)
For coax probes the distance to the wall and to internal fittings is arbitrary.