EasyManua.ls Logo

Endress+Hauser Levelflex FMP53 - Configuration of a level measurement

Endress+Hauser Levelflex FMP53
194 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning via operating menu (On-site display, FieldCare) Levelflex FMP51, FMP52, FMP54
80 Endress+Hauser
10.6 Configuration of a level measurement
F
L
D
E
20mA
100%
4mA
0%
LN
R
A0011360
å 28
Configuration parameters for level measurements in liquids
LN = Length of probe R = Reference point of the measurement
D = Distance E = Empty calibration (= Zero point)
L = Level F = Full calibration (= span)
If for rope probes the DC value is less than 7, then measurement is not possible in the area of
the straining weight. In these cases, the maximum recommended value for the empty
calibration E is LN - 250 mm (LN - 10 in).
Step Parameter Action Description
1
Setup ® Distance unit
Select distance unit.
(® ä 116)
2
Setup ® Operating mode
1)
Select "Level".
(® ä 116)
3
Setup ® Tank type
Select tank type.
(® ä 117)
4
Setup ® Tube diameter
2)
Enter the diameter of the bypass or
stilling well.
(® ä 117)
5
Setup ® Medium group
Select medium group ("water based":
DC>4 or "other": DC³ 1.9)
3)
.
(® ä 117)
6
Setup ® Empty calibration
Enter the distance E between the
reference point R and the minimum level
(0%).
(® ä 119)
7
Setup ® Full calibration
Enter distance F between the minimum
(0%) and maximum (100%) level.
(® ä 120)
8
Setup ® Level
Displays the measured level L.
(® ä 120)
9
Setup ® Distance
Displays the distance D between the
reference point R and the level L.
(® ä 121)

Table of Contents

Other manuals for Endress+Hauser Levelflex FMP53

Related product manuals