Levelflex FMP51, FMP52, FMP54 Commissioning via operating menu (On-site display, FieldCare)
Endress+Hauser 79
After mounting the rod probe in the stilling well or bypass, check and - if necessary - correct the
setting of the reference distance in the unpressurized state. Whilst doing so the level should be at
least 200 mm below the reference distance L
ref
to achieve maximum accuracy.
Step Parameter Action
1
Expert ® Sensor ® Gas phase compensation
® GPC mode
Select the "On" option in order to activate gas phase
compensation.
2
Expert ® Sensor ® Gas phase compensation
® Present reference distance
Check whether the displayed reference distance matches the
nominal value (300 mm or 550 mm, respectively; see the
nameplate).
If yes: nor further actions required.
If no: continue with step 3.
3
Expert ® Sensor ® Gas phase compensation
® Reference distance
Enter the value indicated in "Present reference distance".
For a detailed description of all parameters concerning the gas phase compensation see:
GP01001F, "Levelflex - Description of device parameters - PROFIBUS PA"