Loading...
Description of device parameters (operating menu) Levelflex FMP51, FMP52, FMP54
184 Endress+Hauser
Description
Use this parameter to activate or deactivate the simulation of the switch output.
Options
Off
On
Factory setting
Off (i.e. no simulation)
Switch status
Navigation
Diagnostics ® Simulation ® Switch status
Prerequisite
Only visible for Switch output simulation = On.
Description
Use this parameter to define the switch status for the simulation.
Options
Open
Closed
Factory setting
Open
Simulation device alarm
Navigation
Diagnostics ® Simulation ® Sim. alarm
Description
Use this function to switch the device alarm on and off. In this way, users can verify the correct
adjustment of the current output and the correct function of downstream switching units.
The display alternates between the measured value and a diagnostics message of the "function
check" category (C) while simulation is in progress:
Options
On
Off
Factory setting
Off