Levelflex FMP51, FMP52, FMP54 Description of device parameters (operating menu)
Endress+Hauser 147
Description
Allocates a DI block to the switch output.
Options
• Off
No digital block is allocated.
•
Digital output 1
• Digital output 2
• Digital output 3
• Digital output 4
Factory setting
Off
Assign limit
Navigation
Setup ® Advanced setup ® Switch output ® Assign limit
Prerequisite
Only visible for Switch output function = Limit.
Description
Defines the variable to be checked for limit transgression and allocates it to the switch output.
Options
• Off
No measured variable is allocated.
•
Level linearized
• Distance
• Interface linearized
• Interface distance
• Upper interface thickness
• Terminal voltage
• Electronic temperature
• Relative echo amplitude
• Relative interface amplitude
Factory setting
Off
Assign diagnostic level
Navigation
Setup ® Advanced setup ® Switch output ® Assign diagnostic level
Prerequisite
Only visible for Switch output function = Event level.
Description
Defines to which class of diagnostic events the output reacts.
Options
• Alarm
•
Alarm + warning
• Warning
Factory setting
Alarm