Levelflex FMP51, FMP52, FMP54 Description of device parameters (operating menu)
Endress+Hauser 181
Description
Definition of the logging interval t
log
for data logging. This defines the interval between the
individual data points in the data log, and thus the maximum loggable process time T
log
:
If 1 logging channel is used: T
log
= 1000 × t
log
If 2 logging channels are used: T
log
= 500 × t
log
If 3 logging channels are used: T
log
= 333 × t
log
If 4 logging channels are used: T
log
= 250 × t
log
Once this time elapses, the oldest data points in the data log are cyclically overwritten such that a
time of T
log
always remains in the memory (ring memory principle).
The log contents are cleared if the length of the logging interval is changed.
Input range
1.0 to 3 600.0 s
Factory setting
10.0 s
Additional information
Example
If 1 logging channel is used:
T
log
= 1000 × 1 s = 1 000 s @ 15 min
T
log
= 1000 × 10 s = 10 000 s @ 3 h
T
log
= 1000 × 80 s = 80 000 s @ 1 d
T
log
= 1000 × 3 600 s = 3 600 000 s @ 41 d
Clear logging data
Navigation
Diagnostics ® Data logging ® Clear logging data
Description
Use this function to clear the entire logging data.
Options
Cancel
The data are not cleared. All the data are retained.
Clear data
The logging data are cleared. The logging process starts from scratch.
Factory setting
Cancel
Display channel 1-4
Navigation
Diagnostics ® Data logging ® Display channel 1
Diagnostics ® Data logging ® Display channel 2
Diagnostics ® Data logging ® Display channel 3
Diagnostics ® Data logging ® Display channel 4

Table of Contents