Trouble shooting Levelflex FMP51, FMP52, FMP54
86 Endress+Hauser
Status signals
A0013956
"Failure"
A device error is present. The measured value is no longer valid.
A0013959
"Function check"
The device is in service mode (e.g. during a simulation).
A0013958
"Out of specification"
The device is operated:
•
Outside of its technical specifications (e.g. during startup or a cleaning)
• Outside of the configuration carried out by the user (e.g. level outside configured span)
A0013957
"Maintenance required"
Maintenance is required. The measured value is still valid.
Status symbol (symbol for event level)
A0013961
"Alarm" status
The measurement is interrupted. The signal outputs take on the defined alarm condition. A
diagnostic message is generated.
A0013962
"Warning" status
The device continues to measure. A diagnostic message is generated.
Diagnostics event and event text
The fault can be identified using the diagnostics event. The event text helps you by providing
information about the fault. In addition, the corresponding symbol is displayed before the
diagnostics event.
Diagnostics event
Status symbol Status signal Event number Event text
¯ ¯ ¯
Example
A0013962 A0013958
441 Curr.output 1
3-digit number
If two or more diagnostic messages are pending simultaneously, only the message with the
highest priority is shown. Additional pending diagnostic messages can be shown in the
Diagnostics list submenu (Verweisziel existiert nicht, aber @y.link.required='true').
Past diagnostic messages that are no longer pending are shown in the Event logbook
submenu (Verweisziel existiert nicht, aber @y.link.required='true').
Operating elements
Operating functions in menu, submenu
A0013970
Plus key
Opens the message about the remedial measures.
A0013952
Enter key
Opens the operating menu.