Programming Liquistation CSF48
60
Repetition interval
(only for Daily interval
and Weekly interval)
1 to 999
Factory setting
1
Specify for how many days or weeks the subprogram
should be active.
Example:
Repetition mode = daily interval
Repetition interval = 2
The subprogram is enabled every second day from the
start condition.
If Enable subprogram Interval is selected:
Start condition Options
•No delay
• Date/Time
•Time
Factory setting
Date/Time
No delay:
The subprogram is started when the program is enab-
led.
Date/Time:
Set the start date and start time for enabling the sub-
program.
Time:
Set the start time for enabling the subprogram.
Start date 01.01.2000 to 31.12.2099
Factory setting
DD.MM.YYYY
Set the start date for the 1st interval. The format
depends on the option configured under general set-
tings.
Start time 00:00:00 to 23:59:59
Factory setting
HH:MM:SS (24h)
Set the time for the 1st interval. The format depends
on the option configured under general settings.
Activity time 00-00:01 to 31-00:00
DD-HH:MM
Factory setting
00-00:01 DD-HH:MM
Specify how long the subprogram should be active in
days, hours and minutes. The subprogram always
begins with an activation.
Inactivity time 00-00:01 to 31-00:00
DD-HH:MM
Factory setting
00-00:01 DD-HH:MM
Specify how long the subprogram should be inactive
in days, hours and minutes.
Sample at enable Options
•No
•Yes
Factory setting
Yes
Specify whether the first sample should be taken
directly when the subprogram is enabled.
For example, with intervals, a sample is taken at the
start of every activation interval.
Sample at disable Options
•No
•Yes
Factory setting
No
Specify whether a sample should be taken when the
subprogram is disabled.
For example, with intervals, a sample is taken at the
end of every activation interval.
Path: Menu/Setup/Sampling programs
Function Options Info